The XR06CX, format 32 x 74 x 60 mm, is microprocessor based controller, suitable for applications on medium or low temperature ventilated refrigeratin...
Specifications
BRAND DIXELL

The XR06CX, format 32 x 74 x 60 mm, is microprocessor based controller, suitable for applications on medium or low temperature ventilated refrigerating units. It has three relay outputs to control compressor, fan, and defrost which can be either electrical or reverse cycle (hot gas). The device is also provided with 2 NTC probe inputs, the first one for temperature control and the second one to be located onto the evaporator, to control the defrost termination temperature and to managed the fan and it’s provided with a configurable digital input. With the HOTKEY it’s possible to program the instrument in a quick and easy way. 


- Differential: (0,1°C ? 25°C / 1°F ÷ 45°F) Intervention differential for set point. Compressor Cut is SET POINT + differential. Compressor Cut OUT is when the temperature reaches the

set point.

- Minimum SET POINT: (-55°C÷SET/-67°F÷SET): Sets the minimum value for the set point..

- Maximum SET POINT: (SET÷99°C/ SET÷99°F). Set the maximum value for set point.

- First probe calibration: (-9.9÷9.9°C / -17°F ÷ 17°F) allows to adjust possible offset of the first probe.

- Evaporator probe presence: n= not present; y= the defrost stops by temperature.

- Second probe calibration: (-9.9÷9.9°C / -17°F ÷ 17°F) allows to adjust possible offset of the second probe.

- Outputs activation delay at start up: (0÷99min) This function is enabled at the initial start up of the instrument and inhibits any output activation for the period of time set in the parameter.

- Anti-short cycle delay: (0÷50 min) minimum interval between the compressor stop and the

following restart.

- Compressor ON time with faulty probe: (0÷99 min) time during which the compressor is active

- case of faulty thermostat probe. With Cy=0 compressor is always OFF.

- Compressor OFF time with faulty probe: (0÷99 min) time during which the compressor is OFF

- case of faulty thermostat probe. With Cn=0 compressor is always active.