FILTER DRIER DANFOSS DCL306

FILTER DRIER DANFOSS DCL306

Rp273,000
Brand:DANFOSS
Product Code: DCL306
Stock Instock

Overview

DCL hermetic filter driers are optimised for HFC and HCFC refrigerants and mineral or benzene oils. Compatible with refrigerants R22, R32, R134a, R404...
Specifications
BRAND DANFOSS
CAPACITY (Cu.In) 30
DIMENSION (CM) 8 x 27 x 8,3
INLET CONNECTION 3/4 SAE
MODEL NUMBER DCL 306
NET WEIGHT (KG) 1.45
OUTLET CONNECTION 3/4 SAE
PCN 023Z0156
TECHNOLOGY LIQUID LINE FILTER DRIER
TYPE DESIGNATION FILTER DRIER

DCL hermetic filter driers are optimised for HFC and HCFC refrigerants and mineral or benzene oils. Compatible with refrigerants R22, R32, R134a, R404A, R410A, R407C, R23, R600, R600a, R744, R1234yf, R1234ze, R407f, R290, R452A , R444B, R449A, R448A and R450A. This product is approved for R290, R600 and R600a by ignition source assessment in accordance to standard EN13463-1. Only solder versions (cu-plated / pure copper) and connection sizes below 25 mm are approved for flammable refrigerants. The filter driers are hermetic and approved for up to 46 bar, depending on type. The filter driers are delivered with flare or copper/copper plated steel connections.


Application:

- 80% 3Å Molecular Sieve with 20% activated alumina

- Perfect core blend for systems that operate at high condensing temperatures and require high drying capacity

- Recommended for use with R22, R32, R134a, R404A, R410A, R407C, R23, R600, R600a, R1234yf, R1234ze, R407F, R290, R452A, R444B, R449A, R448A, R450A, R507. For other refrigerants, please contact Danfoss.

- Compatible with the oil types Mineral or AB, POE or PAG without additives. 

The Shell

- UL approved for MWP 667 psig.

- Available with solder (pure copper) connections.

- Outlet connector: 2.8 mm for capillary tube, or can be trimmed for ¼ inch.

- Corrosion resistant powder-painted finish. Special coating for marine applications available upon request.

- Allows installation with any orientation provided the arrow is in the flow direction.

- Available in sizes 1.5 - 5 cubic inches.

The Filter

- 25 µm (0.001 in.) filter provides high retention.with minimal pressure drop.

- Thermally stable up to 250 °F.

 


023Z0156

Product name: Hermetic filter drier

Type: DCL


Acid capacity [g]: 6.23 g

Acid capacity [oz]: 0.22 oz

Activated alum/Molec sieve [%]: 20% / 80%

Approval: UL

Body material: Steel

Brand: ELIMINATOR

Category: Art. 3, par. 3

Connection material: Steel

Core: Solid core

Core Size code: 30 cu.in.

Drying Cap[Drops of Water]24°C: R134a: 888, R290: --, R32: 748, R404A: 925, R407C: 863, R410A: 804, R507: 969

Drying Cap[Drops of Water]52°C R290: --

EAN 5702428159234

Flow Capacity KW: R290: --, R134a: 59.0, R32: 89.9, R404A: 41.5, R407C: 60.4, R410A: 61.4, R507: 40.2

Flow Capacity TR: R134a: 16.8, R290: --, R32: 25.6, R404A: 11.8, R407C: 17.2, R410A: 17.4, R507: 11.4

Flow direction indicator: Label printed 1-way arrow

Fluid Group: II

Gross weight: 1.59 Kg

Inlet 1 connection size [in]: 3/4 in

Inlet connection size [mm]: 19 mm

Inlet connection type: FLARE

LiqCap Cond (ARI 710-2009)[SI]: Delta p=0.07bar tliq= 30°C tvap=-15°C

LiqCapCond (ARI 710-2009)[IMP]: Delta p=1psi tliq= 86°F tvap=5°F

Max. Working Pressure [bar]: 46 bar

Max. Working Pressure [psig]: 667 psig

Net volume [foz US]: 15.68 oz

Net volume [l]: 0.464 L

Net weight: 1.45 Kg

Outlet 1 connection size [in]: 3/4 in

Outlet connection size [mm]: 19 mm

Outlet connection type: FLARE

Packing format: Multi pack

Product description: Liquid line filter drier

Product family name: DCL

Product Group: Filter driers

Product name: Hermetic filter drier

Product type: DCL

Quantity per packing format: 8 pc

Refrigerants: R1234yf, R1234ze, R125, R134a, R22/R407C, R23, R32, R404A, R407A, R407F, R410A, R422B, R422D, R438A, R444B, R448A, R449A, R449B, R450A, R452A, R452B, R454B, R455A, R507A, R513A

Sales restriction: No - Sales restriction exist

Serviceable: No

Shell volume [foz US]: 24.42 oz

Shell volume [l]: 0.72 L

Solid core surface [cm2]: 340 cm2

Solid core surface [in2]: 52.7 in2

Solid core volume [cm3]: 258 cm3

Solid core volume [in3]: 15.77 in3

Specification key: DCL 306

System line application: Liquid line

Temperature range [°C] [Max]: 70 °C

Temperature range [°C] [Min]: -40 °C

Temperature range [°F] [Max]: 160 °F

Temperature range [°F] [Min]: -40 °F

Type designation: DCL 306

UL approval file name: SA6398